RAFAVENT

ATEX Centrifugal Fans

Published product and engineering information

RAFAVENT EXPLOSION-RISK CONFIGURATION

ATEX Centrifugal Fans

Project-specific fan configuration using an ATEX-certified motor for classified-area ventilation. The complete fan assembly is not claimed as ATEX certified.

← ATEX Fans

Certification boundary: only the motor certificate and marking supplied for the selected motor may be described as ATEX certified. Fan assembly conformity requires a separate assessment and valid evidence for the complete configuration.

ATEX project data schedule

Required fieldProject definition
Zone1 / 2 or 21 / 22 — project input
HazardGas or dust — project input
Equipment category2G / 3G or 2D / 3D — motor certificate
EPLGb / Gc or Db / Dc — motor certificate
GroupIIA / IIB / IIC or IIIA / IIIB / IIIC
Temperature classT1–T6 or maximum surface temperature
Motor Ex protectionEx db / Ex eb / Ex ec / Ex tb — exact certificate
Ambient rangeMotor certificate + project condition
Electrical dataVoltage, phase, frequency, VFD compatibility
Fan constructionMaterials, clearances and spark-risk review
Evidence statusMotor certificate available; complete fan not certified

Selection and release process

  1. Confirm classified zone and hazardous substance.
  2. Select the base RAFAVENT fan from the required airflow and pressure.
  3. Select the certified Ex motor from its certificate and marking.
  4. Review materials, clearances, earthing, guards and control method.
  5. Issue the project submittal with a clear certification boundary.
Send project requirements