Indoor Air Treatment

Published product and engineering information

Indoor Air Treatment

Engineered indoor-air treatment packages for filtration, recirculation and project-critical applications. Selection is based on the real system pressure budget and the exact documented filter package.

Filter fan unit

Double-skin casing with staged particulate filtration and a fan selected for clean and final filter resistance.

Recirculation module

Indoor recirculation package with service access, differential-pressure monitoring and project-specific controls.

HEPA / critical package

Final-stage high-efficiency filtration only when the exact filter class, housing sealing and test method are documented.

Preliminary model envelope

ModelAirflow m³/hAvailable static pressure PaMotor kWSound dB(A) @ 3 mTypical scope
RF-IAU-25001,500–3,000250–5001.5–2.254Compact filter/fan package
RF-IAU-50003,000–6,500300–6503–5.560Medium-duty air-treatment package
RF-IAU-100006,000–12,000400–8007.5–1568Large double-skin package
RF-IAU-2000012,000–24,000500–1,00018.5–3076Project-engineered modular package

Filtration design inputs

ItemEngineering requirement
Contaminant / particle targetDefine by application; no health claim is assumed
Outdoor / return-air ratioRequired at minimum, normal and maximum duty
Filter stagesPrefilter, fine filter and optional final HEPA stage as documented
Filter classificationRequested ISO 16890 group or HEPA class only for the exact selected filter
Pressure dropClean, recommended change and final allowable ΔP for every stage
Casing / bypassHousing leakage and filter bypass acceptance criteria
MonitoringDifferential-pressure gauge/switch and BMS alarm requirement
MaintenanceAccess side, replacement clearance, drain and condensate provisions

System pressure budget

Pressure componentSelection basis
Ductwork and fittingsFrom coordinated system calculation
Coils / heat exchangersAt design airflow and fluid condition
FiltersAll stages at clean and final resistance
Silencers and terminalsInclude actual selected components
Control devicesDampers, louvers and other accessories
Selection reserveProject-defined; must not hide missing data

ΔP system = ducts + coils + filters (clean/final) + silencers + terminals + control devices + reserve

Required project data

InputRequired detail
Air dutyAirflow, external static pressure, operating hours and diversity
Air conditionTemperature, humidity, particle loading, corrosive or hazardous content
Electrical / controlsSupply, starter or VFD, sensors, BMS protocol and alarm logic
ConstructionIndoor/outdoor location, casing, access, drainage, coating and sound limit
Evidence packageExact filter datasheet, certificates, leakage/test requirement and acceptance criteria

RAFAVENT
Engineering boundary: Values above are preliminary calculated, non-certified selection envelopes. Filter classification belongs only to the exact documented filter. RAFAVENT makes no infection-control, virus-removal, sterilization, UV-C dose, ionization or ozone claim without valid evidence for the exact component and complete system. UV-C or ionization, if requested, is project-specific and not standard.

Send the airflow, pressure budget, filter stages and acceptance criteria for a project-specific selection.