RAFAVENT

Louvers, Dampers & Air-Terminal Products

Published product and engineering information

RAFAVENT AIR DISTRIBUTION & CONTROL

Louvers, Dampers & Air-Terminal Products

Project-sized louvers, airflow-control dampers, grilles and air-terminal products coordinated with opening dimensions, airflow, pressure loss, weather exposure and architectural requirements.

Performance boundary: dimensions, free area and velocities below are preliminary selection envelopes, not AMCA-certified ratings. Air performance, leakage, water penetration, wind-driven rain or acoustic claims require valid test data for the exact model and size.

Product families

Weather and drainable louvers

Outdoor intake or discharge products selected from face area, free area, pressure loss and rain exposure.

Control and isolation dampers

Parallel- or opposed-blade assemblies with manual or motorized actuation selected for system pressure and control duty.

Grilles and air terminals

Supply, return and extract terminals coordinated with velocity, throw, pressure loss, sound and architectural finish.

Required project data

Required fieldProject definition
Opening and installationClear width × height, wall/duct depth, flange, fixing and multi-section limits
Air dutyAirflow, intake/exhaust direction, face velocity and allowable pressure loss
Weather exposureIndoor/outdoor, rain, wind-driven rain, sand, insects and drainage path
ConstructionGalvanized steel, aluminium or stainless steel; blade/frame thickness and finish
Damper operationParallel/opposed blade, manual/electric/pneumatic actuator, fail position and torque
Performance evidenceFree-area calculation, pressure loss, leakage, water penetration and acoustic data as applicable
AccessoriesBird screen, insect screen, filter, sill, flange, actuator, end switch and access
Compliance statusNo AMCA or leakage/water rating claim without exact valid model evidence

Preliminary manufacturing and selection envelope

ModelProductNominal depthSingle-section size envelopeFree-area basisInitial velocity basis
RF-LV-100Weather louver100 mm300×300 to 2,000×2,000 mm40–55% calculated1.5–2.5 m/s intake basis
RF-DL-150Drainable louver150 mm300×300 to 2,000×2,000 mm45–60% calculated1.5–2.5 m/s intake basis
RF-CD-100Control damper100 / 150 mm200×200 to 2,000×2,000 mmProject geometry2–10 m/s duct basis
RF-AT-50Grille / air terminal50–100 mm100×100 to 1,200×600 mmProject geometry1.5–4 m/s face basis

Sizing and submittal calculations

ItemEquation / required outputEngineering note
Face areaAface = width × heightUse clear project opening dimensions.
Face velocityVface = Q / (3,600 × Aface)Q in m³/h and area in m².
Free areaAfree = measured/calculated open passage areaDo not infer pressure loss from percentage alone.
Free-area velocityVfree = Q / (3,600 × Afree)Use for tested water-penetration comparison only with valid product data.
Pressure lossΔP from exact model/size test data or approved calculationScreen, blade shape and installation affect resistance.
Damper torqueActuator torque ≥ blade/linkage torque × approved safety factorConfirm system pressure, seals, orientation and fail position.
SectioningDefine mullions, joint details, drainage and structural supportLarge openings require coordinated fabrication drawings.

Engineering release workflow

  1. Confirm the opening schedule, airflow and installation exposure.
  2. Select the product type, blade geometry, materials and accessories.
  3. Calculate face/free-area velocities and preliminary pressure loss.
  4. Verify actuator, leakage, rain, acoustic or structural evidence where required.
  5. Issue coordinated dimensions, finish, accessories and claim status in the submittal.
Send opening schedule and airflow data