Technical documents and dimensions
Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.
Published product and engineering information
RAFAVENT CENTRIFUGAL FAN SUBFAMILY
SISW · SINGLE INLET · SINGLE WIDTH
Single-inlet, single-width (SISW) forward-curved centrifugal fans for model-specific ventilation duties.
Preliminary engineering selection dataRAFAVENT RF-CF-FWD SERIES
Compact forward-curved centrifugal fans for cabinets, AHUs and low-to-medium pressure HVAC supply or extract duties.
| Model | Wheel Ø mm | rpm | Recommended Q m³/h | Recommended Ps Pa | Calculated max Q | Calculated peak Ps | Est. shaft kW | Preliminary motor selection kW | Supply | Est. LpA @3m dB(A) | Drive basis |
|---|---|---|---|---|---|---|---|---|---|---|---|
| RF-CF-FWD-200 | 200 | 1450 | 140–274 | 46–108 | 334 | 131 | 0.01 | 0.12 | 230/400 V 3Ph | 51 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-250 | 250 | 1450 | 274–535 | 72–168 | 652 | 205 | 0.03 | 0.12 | 230/400 V 3Ph | 51 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-315 | 315 | 1450 | 548–1,070 | 114–267 | 1,305 | 326 | 0.09 | 0.12 | 230/400 V 3Ph | 52 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-355 | 355 | 1450 | 785–1,532 | 145–340 | 1,868 | 414 | 0.17 | 0.25 | 230/400 V 3Ph | 54 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-400 | 400 | 1450 | 1,123–2,192 | 184–431 | 2,673 | 526 | 0.3 | 0.37 | 230/400 V 3Ph | 56 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-450 | 450 | 1450 | 1,598–3,120 | 233–546 | 3,805 | 665 | 0.54 | 0.75 | 230/400 V 3Ph | 58 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-500 | 500 | 1450 | 2,192–4,280 | 287–674 | 5,220 | 821 | 0.92 | 1.1 | 230/400 V 3Ph | 60 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-560 | 560 | 960 | 2,039–3,981 | 158–370 | 4,855 | 452 | 0.47 | 0.55 | 230/400 V 3Ph | 57 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-630 | 630 | 960 | 2,904–5,669 | 200–469 | 6,913 | 572 | 0.85 | 1.1 | 230/400 V 3Ph | 59 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-710 | 710 | 960 | 4,156–8,114 | 254–595 | 9,896 | 726 | 1.54 | 2.2 | 230/400 V 3Ph | 61 ±6 | Direct / belt by arrangement |
| RF-CF-FWD-800 | 800 | 720 | 4,459–8,706 | 181–425 | 10,617 | 518 | 1.18 | 1.5 | 230/400 V 3Ph | 59 ±6 | Direct / belt by arrangement |
Forward-curved fans can have rising motor demand toward open flow. Motor selection includes a preliminary 15% margin but final absorbed-power review across the operating range is mandatory. Estimated sound at 3 m has ±6 dB(A) uncertainty before casing, duct and system effects.
Open a model to view its six-point preliminary Q–Ps curve.
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 76 |
| 2 | 67 | 108 |
| 3 | 134 | 131 |
| 4 | 200 | 116 |
| 5 | 267 | 74 |
| 6 | 334 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 119 |
| 2 | 130 | 168 |
| 3 | 261 | 205 |
| 4 | 392 | 181 |
| 5 | 522 | 115 |
| 6 | 652 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 189 |
| 2 | 261 | 267 |
| 3 | 522 | 326 |
| 4 | 783 | 287 |
| 5 | 1,044 | 183 |
| 6 | 1,305 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 240 |
| 2 | 374 | 340 |
| 3 | 747 | 414 |
| 4 | 1,121 | 364 |
| 5 | 1,495 | 232 |
| 6 | 1,868 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 305 |
| 2 | 535 | 431 |
| 3 | 1,069 | 526 |
| 4 | 1,604 | 463 |
| 5 | 2,138 | 294 |
| 6 | 2,673 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 386 |
| 2 | 761 | 546 |
| 3 | 1,522 | 665 |
| 4 | 2,283 | 585 |
| 5 | 3,044 | 373 |
| 6 | 3,805 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 476 |
| 2 | 1,044 | 674 |
| 3 | 2,088 | 821 |
| 4 | 3,132 | 723 |
| 5 | 4,176 | 460 |
| 6 | 5,220 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 262 |
| 2 | 971 | 370 |
| 3 | 1,942 | 452 |
| 4 | 2,913 | 397 |
| 5 | 3,884 | 253 |
| 6 | 4,855 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 332 |
| 2 | 1,383 | 469 |
| 3 | 2,765 | 572 |
| 4 | 4,148 | 503 |
| 5 | 5,531 | 320 |
| 6 | 6,913 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 421 |
| 2 | 1,979 | 595 |
| 3 | 3,958 | 726 |
| 4 | 5,937 | 639 |
| 5 | 7,916 | 407 |
| 6 | 9,896 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 301 |
| 2 | 2,123 | 425 |
| 3 | 4,247 | 518 |
| 4 | 6,370 | 456 |
| 5 | 8,493 | 290 |
| 6 | 10,617 | 0 |
Confirm airflow, static pressure, air density, temperature, inlet arrangement, drive side, rotation, discharge position, motor rated output, voltage/phase, VFD method, operating range, corrosion class, permissible sound level and access space before order.
Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.
Provide level support, flexible connections, guarded drive components, alignment checks and safe maintenance access. Follow the approved project-specific O&M document.
Selection tables and calculated curves on this page are preliminary engineering guidance, not certified RAFAVENT test ratings. Confirm the operating point and controlled documents before order.