RAFAVENT CENTRIFUGAL FAN SUBFAMILY

Single-Inlet Forward-Curved Centrifugal Fans

SISW · SINGLE INLET · SINGLE WIDTH

Single-inlet, single-width (SISW) forward-curved centrifugal fans for model-specific ventilation duties.

Preliminary engineering selection data
RAFAVENT single-inlet forward-curved centrifugal fan
RAFAVENT single-inlet forward-curved centrifugal fan.

RAFAVENT RF-CF-FWD SERIES

Single-Inlet Forward-Curved Centrifugal Fans — Technical Selection Data

Compact forward-curved centrifugal fans for cabinets, AHUs and low-to-medium pressure HVAC supply or extract duties.

RAFAVENT Engineering Calculation — Preliminary Selection — Non-Certified. Values are calculated at 20 °C and standard air density 1.20 kg/m³ using fan-law scaling and engineering assumptions. They are not laboratory-certified ratings. No efficiency claim is made. Final selection requires a confirmed duty point, inlet arrangement, motor loading review and approved production drawing.

Construction and application

  • Formed steel scroll casing with single inlet and multi-blade forward-curved wheel; double-inlet execution requires separate engineering.
  • Wheel balancing and vibration acceptance are required before dispatch.
  • Direct or belt drive by arrangement. Confirm drive side, clockwise/counter-clockwise rotation and discharge position when viewed from the inlet.
  • Motor table shows rated output, not absorbed electrical input. VFD use requires motor and minimum-speed confirmation.
  • Preliminary clean-air ambient duty −20 to +50 °C. No ATEX, smoke, furnace or high-temperature certification is claimed.
  • Standard model series Ø200–Ø800. Sizes 900–1000 are custom only after structural, shaft and motor review.

Model selection table

ModelWheel Ø mmrpmRecommended Q m³/hRecommended Ps PaCalculated max QCalculated peak PsEst. shaft kWPreliminary motor selection kWSupplyEst. LpA @3m dB(A)Drive basis
RF-CF-FWD-2002001450140–27446–1083341310.010.12230/400 V 3Ph51 ±6Direct / belt by arrangement
RF-CF-FWD-2502501450274–53572–1686522050.030.12230/400 V 3Ph51 ±6Direct / belt by arrangement
RF-CF-FWD-3153151450548–1,070114–2671,3053260.090.12230/400 V 3Ph52 ±6Direct / belt by arrangement
RF-CF-FWD-3553551450785–1,532145–3401,8684140.170.25230/400 V 3Ph54 ±6Direct / belt by arrangement
RF-CF-FWD-40040014501,123–2,192184–4312,6735260.30.37230/400 V 3Ph56 ±6Direct / belt by arrangement
RF-CF-FWD-45045014501,598–3,120233–5463,8056650.540.75230/400 V 3Ph58 ±6Direct / belt by arrangement
RF-CF-FWD-50050014502,192–4,280287–6745,2208210.921.1230/400 V 3Ph60 ±6Direct / belt by arrangement
RF-CF-FWD-5605609602,039–3,981158–3704,8554520.470.55230/400 V 3Ph57 ±6Direct / belt by arrangement
RF-CF-FWD-6306309602,904–5,669200–4696,9135720.851.1230/400 V 3Ph59 ±6Direct / belt by arrangement
RF-CF-FWD-7107109604,156–8,114254–5959,8967261.542.2230/400 V 3Ph61 ±6Direct / belt by arrangement
RF-CF-FWD-8008007204,459–8,706181–42510,6175181.181.5230/400 V 3Ph59 ±6Direct / belt by arrangement

Forward-curved fans can have rising motor demand toward open flow. Motor selection includes a preliminary 15% margin but final absorbed-power review across the operating range is mandatory. Estimated sound at 3 m has ±6 dB(A) uncertainty before casing, duct and system effects.

Calculated model curves

Open a model to view its six-point preliminary Q–Ps curve.

RF-CF-FWD-200 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
1076
267108
3134131
4200116
526774
63340
RF-CF-FWD-250 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10119
2130168
3261205
4392181
5522115
66520
RF-CF-FWD-315 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10189
2261267
3522326
4783287
51,044183
61,3050
RF-CF-FWD-355 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10240
2374340
3747414
41,121364
51,495232
61,8680
RF-CF-FWD-400 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10305
2535431
31,069526
41,604463
52,138294
62,6730
RF-CF-FWD-450 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10386
2761546
31,522665
42,283585
53,044373
63,8050
RF-CF-FWD-500 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10476
21,044674
32,088821
43,132723
54,176460
65,2200
RF-CF-FWD-560 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10262
2971370
31,942452
42,913397
53,884253
64,8550
RF-CF-FWD-630 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10332
21,383469
32,765572
44,148503
55,531320
66,9130
RF-CF-FWD-710 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10421
21,979595
33,958726
45,937639
57,916407
69,8960
RF-CF-FWD-800 — calculated Q–Ps curve
Airflow Q (m³/h)Static pressure Ps (Pa)
PointQ (m³/h)Ps (Pa)
10301
22,123425
34,247518
46,370456
58,493290
610,6170

Selection requirements

Confirm airflow, static pressure, air density, temperature, inlet arrangement, drive side, rotation, discharge position, motor rated output, voltage/phase, VFD method, operating range, corrosion class, permissible sound level and access space before order.

Technical documents, dimensions and service

Technical documents and dimensions

Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.

Installation and maintenance

Provide level support, flexible connections, guarded drive components, alignment checks and safe maintenance access. Follow the approved project-specific O&M document.

Selection tables and calculated curves on this page are preliminary engineering guidance, not certified RAFAVENT test ratings. Confirm the operating point and controlled documents before order.

Information required before selection

  • Required airflow and static pressure
  • Operating temperature and conveyed-air composition
  • Installation orientation, space and connection details
  • Electrical supply, control method and duty pattern
  • Sound, material and environmental constraints