Technical documents and dimensions
Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.
Published product and engineering information
RAFAVENT FAN FAMILY
Plug-fan arrangements for integration into air-handling or process enclosures.
Preliminary engineering dataRAFAVENT RF-PF-BC-D SERIES
Direct-driven, free-running backward-curved impellers for integration into AHU, ventilation and process plenums.
| Model | Wheel Ø mm | Nominal max rpm | Recommended Q m³/h | Recommended Ps Pa | Calculated max Q | Calculated shutoff Ps | Est. shaft kW | Preliminary motor selection kW | Supply | Assembly LpA; test data required | Drive basis |
|---|---|---|---|---|---|---|---|---|---|---|---|
| RF-PF-BC-D-250 | 250 | 2800 | 570–1,335 | 261–696 | 1,628 | 870 | 0.26 | 0.37 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-280 | 280 | 2500 | 715–1,674 | 261–696 | 2,042 | 870 | 0.33 | 0.55 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-315 | 315 | 2200 | 895–2,098 | 256–683 | 2,558 | 853 | 0.41 | 0.55 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-355 | 355 | 1950 | 1,136–2,661 | 255–681 | 3,245 | 851 | 0.51 | 0.75 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-400 | 400 | 1750 | 1,458–3,416 | 261–696 | 4,166 | 870 | 0.68 | 1.1 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-450 | 450 | 1550 | 1,839–4,308 | 259–691 | 5,254 | 864 | 0.85 | 1.1 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-500 | 500 | 1400 | 2,278–5,338 | 261–696 | 6,510 | 870 | 1.06 | 1.5 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-560 | 560 | 1250 | 2,858–6,696 | 261–696 | 8,166 | 870 | 1.32 | 2.2 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-630 | 630 | 1100 | 3,581–8,390 | 256–683 | 10,232 | 853 | 1.63 | 2.2 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-710 | 710 | 980 | 4,567–10,699 | 258–688 | 13,048 | 860 | 2.09 | 3 | 230/400 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
| RF-PF-BC-D-800 | 800 | 880 | 5,866–13,744 | 264–704 | 16,761 | 880 | 2.75 | 4 | 400/690 V 3Ph | Test data required | Direct IEC/VFD or engineered EC option |
Verified acoustic performance for this configuration has not been published. The previous 56–61 dB values and assumed ±6 dB uncertainty have no documented test basis and are not valid acoustic selection ratings. The lined enclosure is intended to reduce casing-radiated sound; inlet and outlet attenuation depends on ductwork and silencers. Compare enclosed and bare-core configurations at the same airflow, pressure, speed and installation conditions. LwA is sound power and LpA is sound pressure; LpA also requires distance, measurement environment and sound path. Specify frequency bands and test method. Tabulated speed is a calculation reference, not an approved maximum mechanical speed.
Open a model to view its six-point preliminary Q–Ps curve.
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 870 |
| 2 | 326 | 853 |
| 3 | 651 | 792 |
| 4 | 976 | 670 |
| 5 | 1,302 | 461 |
| 6 | 1,628 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 870 |
| 2 | 408 | 853 |
| 3 | 817 | 792 |
| 4 | 1,225 | 670 |
| 5 | 1,633 | 461 |
| 6 | 2,042 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 853 |
| 2 | 512 | 836 |
| 3 | 1,023 | 776 |
| 4 | 1,535 | 657 |
| 5 | 2,046 | 452 |
| 6 | 2,558 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 851 |
| 2 | 649 | 834 |
| 3 | 1,298 | 775 |
| 4 | 1,947 | 656 |
| 5 | 2,596 | 451 |
| 6 | 3,245 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 870 |
| 2 | 833 | 853 |
| 3 | 1,667 | 792 |
| 4 | 2,500 | 670 |
| 5 | 3,333 | 461 |
| 6 | 4,166 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 864 |
| 2 | 1,051 | 847 |
| 3 | 2,102 | 787 |
| 4 | 3,153 | 666 |
| 5 | 4,203 | 458 |
| 6 | 5,254 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 870 |
| 2 | 1,302 | 853 |
| 3 | 2,604 | 792 |
| 4 | 3,906 | 670 |
| 5 | 5,208 | 461 |
| 6 | 6,510 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 870 |
| 2 | 1,633 | 853 |
| 3 | 3,266 | 792 |
| 4 | 4,900 | 670 |
| 5 | 6,533 | 461 |
| 6 | 8,166 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 853 |
| 2 | 2,046 | 836 |
| 3 | 4,093 | 776 |
| 4 | 6,139 | 657 |
| 5 | 8,186 | 452 |
| 6 | 10,232 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 860 |
| 2 | 2,610 | 843 |
| 3 | 5,219 | 783 |
| 4 | 7,829 | 662 |
| 5 | 10,438 | 456 |
| 6 | 13,048 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 880 |
| 2 | 3,352 | 863 |
| 3 | 6,704 | 801 |
| 4 | 10,056 | 678 |
| 5 | 13,409 | 467 |
| 6 | 16,761 | 0 |
Confirm airflow, static pressure, air density, temperature, plenum dimensions, inlet approach, inlet-cone geometry, discharge clearance, motor location and cooling, rated motor output, voltage/phase, VFD or EC control method, operating range, corrosion class, permissible sound level and access space before order.
Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.
Provide level support, flexible connections, guarded drive components, alignment checks and safe maintenance access. Follow the approved project-specific O&M document.
Selection tables and calculated curves on this page are preliminary engineering guidance, not certified RAFAVENT test ratings. Confirm the operating point and controlled documents before order.