Technical documents and dimensions
Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.
Published product and engineering information
RAFAVENT INLINE & ACOUSTIC SUBFAMILY
Fan units designed for direct integration into circular or rectangular duct routes.
Preliminary engineering dataRAFAVENT RF-ID-MF SERIES
Compact direct-driven mixed-flow units for circular duct supply and extract duties.
| Model | Impeller Ø mm | rpm | Recommended Q m³/h | Recommended Ps Pa | Calculated max Q | Calculated shutoff Ps | Est. shaft kW | Preliminary motor selection kW | Supply | Est. LpA @3m dB(A) | Arrangement |
|---|---|---|---|---|---|---|---|---|---|---|---|
| RF-ID-MF-200 | 200 | 2800 | 235–551 | 104–290 | 672 | 371 | 0.05 | 0.12 | 230 V 1Ph | 52 ±6 | Direct mixed-flow |
| RF-ID-MF-250 | 250 | 2800 | 459–1,076 | 162–453 | 1,312 | 580 | 0.15 | 0.18 | 230 V 1Ph | 56 ±6 | Direct mixed-flow |
| RF-ID-MF-280 | 280 | 2800 | 645–1,512 | 204–568 | 1,844 | 728 | 0.26 | 0.37 | 230 V 1Ph | 58 ±6 | Direct mixed-flow |
| RF-ID-MF-315 | 315 | 2800 | 919–2,153 | 258–719 | 2,625 | 921 | 0.47 | 0.55 | 230 V 1Ph | 60 ±6 | Direct mixed-flow |
| RF-ID-MF-350 | 350 | 1450 | 653–1,529 | 85–238 | 1,865 | 305 | 0.11 | 0.18 | 230/400 V 3Ph | 53 ±6 | Direct mixed-flow |
| RF-ID-MF-400 | 400 | 1450 | 974–2,283 | 112–311 | 2,784 | 398 | 0.22 | 0.25 | 230/400 V 3Ph | 55 ±6 | Direct mixed-flow |
| RF-ID-MF-450 | 450 | 1450 | 1,387–3,250 | 141–393 | 3,964 | 504 | 0.39 | 0.55 | 230/400 V 3Ph | 58 ±6 | Direct mixed-flow |
| RF-ID-MF-500 | 500 | 1450 | 1,903–4,459 | 174–486 | 5,438 | 623 | 0.66 | 1.1 | 230/400 V 3Ph | 59 ±6 | Direct mixed-flow |
Selected motor includes a preliminary 15% margin. Estimated sound at 3 m has ±6 dB(A) uncertainty before duct, attenuation, room and installation effects.
Open a model to view its six-point preliminary Q–Ps curve.
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 371 |
| 2 | 134 | 364 |
| 3 | 269 | 334 |
| 4 | 403 | 279 |
| 5 | 538 | 186 |
| 6 | 672 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 580 |
| 2 | 262 | 569 |
| 3 | 525 | 522 |
| 4 | 788 | 435 |
| 5 | 1,050 | 290 |
| 6 | 1,312 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 728 |
| 2 | 369 | 713 |
| 3 | 738 | 655 |
| 4 | 1,106 | 546 |
| 5 | 1,475 | 364 |
| 6 | 1,844 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 921 |
| 2 | 525 | 903 |
| 3 | 1,050 | 829 |
| 4 | 1,575 | 691 |
| 5 | 2,100 | 461 |
| 6 | 2,625 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 305 |
| 2 | 373 | 299 |
| 3 | 746 | 275 |
| 4 | 1,119 | 229 |
| 5 | 1,492 | 153 |
| 6 | 1,865 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 398 |
| 2 | 557 | 390 |
| 3 | 1,114 | 359 |
| 4 | 1,670 | 299 |
| 5 | 2,227 | 199 |
| 6 | 2,784 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 504 |
| 2 | 793 | 494 |
| 3 | 1,586 | 454 |
| 4 | 2,378 | 378 |
| 5 | 3,171 | 252 |
| 6 | 3,964 | 0 |
| Point | Q (m³/h) | Ps (Pa) |
|---|---|---|
| 1 | 0 | 623 |
| 2 | 1,088 | 610 |
| 3 | 2,175 | 560 |
| 4 | 3,262 | 467 |
| 5 | 4,350 | 311 |
| 6 | 5,438 | 0 |
Confirm airflow, static pressure, air density, temperature, duct diameter, upstream and downstream straight length, mounting orientation, service access, voltage/phase, speed-control method, operating range, permissible sound level and conveyed-air composition before order.
Final dimensions, connection details, materials, motor data and project drawings are issued for the selected configuration after engineering review.
Provide level support, flexible connections, guarded drive components, alignment checks and safe maintenance access. Follow the approved project-specific O&M document.
Selection tables and calculated curves on this page are preliminary engineering guidance, not certified RAFAVENT test ratings. Confirm the operating point and controlled documents before order.