Subfamily scope
Stairwell Pressurisation Fans
This page is reserved for verified technical and commercial documents for this RAFAVENT subfamily.
Published product and engineering information
RAFAVENT JET & SMOKE-CONTROL SUBFAMILY
Air-movement equipment for project-specific staircase and protected-route pressurisation systems.
Documentation workspaceSubfamily scope
This page is reserved for verified technical and commercial documents for this RAFAVENT subfamily.
Technical document centre
Verified construction and selection fields
Files will be published after engineering review and document approval.Airflow and pressure data by confirmed model
Files will be published after engineering review and document approval.Installation dimensions and available CAD files
Files will be published after engineering review and document approval.Controlled catalogue release for this subfamily
Files will be published after engineering review and document approval.Only certificates applicable to the supplied configuration
Files will be published after engineering review and document approval.Installation, operation and maintenance instructions
Files will be published after engineering review and document approval.Calculated guidance for system screening only. Final pressure targets, open-door airflow, relief area, fan duty and control sequence must be verified against the project fire strategy and applicable local standard.
| Scenario | Engineering basis | Release condition |
|---|---|---|
| Closed-door pressure control | Differential-pressure sensor + VFD control | Project fire strategy and approved cause-and-effect |
| Open-door make-up airflow | Door-area and required escape-route air velocity | Project fire strategy and approved cause-and-effect |
| Pressure relief / bypass | Relief damper / bypass sized for maximum pressure | Project fire strategy and approved cause-and-effect |
| Commissioning and cause-effect test | Measured pressure, airflow, door force and alarm sequence | Project fire strategy and approved cause-and-effect |
| Model | Max airflow (m³/h) | Reference static pressure (Pa) | Motor estimate (kW) | Control |
|---|---|---|---|---|
| RF-SP-315 | 4,500 | 650 | 1.5 | VFD + pressure sensor |
| RF-SP-400 | 7,500 | 750 | 3 | VFD + pressure sensor |
| RF-SP-450 | 10,000 | 800 | 4 | VFD + pressure sensor |
| RF-SP-500 | 14,000 | 900 | 5.5 | VFD + pressure sensor |
| RF-SP-560 | 19,000 | 1000 | 7.5 | VFD + pressure sensor |
| RF-SP-630 | 26,000 | 1100 | 11 | VFD + pressure sensor |
| Input | Symbol | Illustrative value | Status |
|---|---|---|---|
| Effective leakage area | A | 0.35 m² | Project input |
| Target pressure difference | ΔP | 50 Pa | Illustrative only |
| Discharge coefficient | Cd | 0.65 | Verify |
| Calculated leakage flow | Q | ≈2,050 m³/h | Preliminary |
| State | Fan command | Damper / relief | Verification |
|---|---|---|---|
| Standby | Project-defined | Normal position | BMS healthy |
| Fire alarm | Start / duty command | Open required path | Alarm feedback |
| Door closed | Modulate to pressure setpoint | Relieve excess pressure | Pressure + door force |
| Door open | Increase to airflow demand | Coordinate relief | Air velocity |
| Sensor fault | Approved fallback speed | Safe position | Fault alarm |
| Component | Minimum project definition |
|---|---|
| Supply fan | Duty, redundancy, motor, VFD |
| Pressure sensor | Range, location, redundancy |
| Relief path | Damper or bypass free area |
| Controls | Panel, cause-and-effect, fire alarm interface |
| Power | Normal/emergency supply and isolation |
| Test | Record |
|---|---|
| Closed-door differential pressure | Pa at representative floors |
| Open-door airflow / velocity | m³/h and m/s |
| Door opening force | Measured result |
| Alarm and feedback | Cause-and-effect result |
| Power failure / recovery | Sequence result |
| Speed | Airflow (m³/h) | Static pressure (Pa) |
|---|---|---|
| 0 | 0 | 650 |
| 25 | 1125 | 611 |
| 50 | 2250 | 488 |
| 75 | 3375 | 286 |
| 100 | 4500 | 0 |
| Speed | Airflow (m³/h) | Static pressure (Pa) |
|---|---|---|
| 0 | 0 | 750 |
| 25 | 1875 | 705 |
| 50 | 3750 | 563 |
| 75 | 5625 | 330 |
| 100 | 7500 | 0 |
| Speed | Airflow (m³/h) | Static pressure (Pa) |
|---|---|---|
| 0 | 0 | 800 |
| 25 | 2500 | 752 |
| 50 | 5000 | 600 |
| 75 | 7500 | 352 |
| 100 | 10000 | 0 |
| Speed | Airflow (m³/h) | Static pressure (Pa) |
|---|---|---|
| 0 | 0 | 900 |
| 25 | 3500 | 846 |
| 50 | 7000 | 675 |
| 75 | 10500 | 396 |
| 100 | 14000 | 0 |
| Speed | Airflow (m³/h) | Static pressure (Pa) |
|---|---|---|
| 0 | 0 | 1000 |
| 25 | 4750 | 940 |
| 50 | 9500 | 750 |
| 75 | 14250 | 440 |
| 100 | 19000 | 0 |
| Speed | Airflow (m³/h) | Static pressure (Pa) |
|---|---|---|
| 0 | 0 | 1100 |
| 25 | 6500 | 1034 |
| 50 | 13000 | 825 |
| 75 | 19500 | 484 |
| 100 | 26000 | 0 |